Wireman · Box fill calculator · 2023 NEC ·
Raceway & boxes
Box fill calculator
Count what's going in the box. Every item gets its own line, so you can see exactly where the room goes.
How this is calculated
- Volume allowances per conductor come from Table 314.16(B)(1). Standard metal box volumes come from Table 314.16(A).
- Each conductor that starts outside the box and ends or is spliced inside counts once. A conductor that passes through unbroken counts once, or twice if it's looped 12 in. or longer.
- One or more internal clamps count once, based on the largest conductor. Each support fitting counts once.
- Each device yoke counts twice, based on the largest conductor connected to it.
- All equipment grounding conductors together count once, based on the largest. Isolated-ground conductors per 250.146(D) add one more.