Wireman · A/C outdoor unit won’t run: troubleshooting for electricians · 2023 NEC ·
A/C outdoor unit won’t run
Split it at the contactor: is the 24 V call arriving, and is 240 V getting through?
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
When the thermostat calls for cooling, it connects R to Y. That 24 V signal travels from the furnace or air handler out to the condenser and energizes the contactor coil, which closes and sends 240 V to the compressor and fan. The indoor blower runs separately on G. So the outdoor unit needs two things at once: line voltage from its own breaker and disconnect, and the 24 V call from the indoor unit’s transformer.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- With the thermostat set to cool, is the indoor blower running?
- Yes, air is blowing insideTest: Measure 24 V at the contactor coilExpect: About 24 V AC (often 24 to 28 V).
- 0 V at the coilTest: Check Y at the indoor boardExpect: About 24 V while cooling is called for.
- 24 V at Y indoorsOpen Y circuit between the indoor unit and the contactor
- 0 V at Y indoorsThe thermostat isn’t sending a cooling call
- 24 V, contactor not pulled inFailed contactor coil or stuck contactor
- 24 V, contactor pulled inTest: Measure line and load side of the contactorExpect: About 240 V (or 208 V) on both sides.
- No voltage on the line sideTest: Check the disconnectExpect: About 240 V coming in and going out.
- Voltage in, none outBlown fuses or a bad disconnect
- No voltage coming inNo power from the panel
- Line side good, load side low or 0Burned or pitted contactor contacts
- Both sides goodWith 240 V on the load side, what do the compressor and fan do?
- Fan runs, compressor doesn’tThe compressor isn’t starting
- Compressor runs, fan doesn’tThe condenser fan isn’t running
- Both hum, neither startsLikely a failed dual run capacitor
- Silent, nothing tries to startOpen wiring after the contactor
- No voltage on the line sideTest: Check the disconnectExpect: About 240 V coming in and going out.
- 0 V at the coilTest: Check Y at the indoor boardExpect: About 24 V while cooling is called for.
- No, nothing runs inside or outNo 24 V control power
- Thermostat is blankNo 24 V control power
- Yes, air is blowing insideTest: Measure 24 V at the contactor coilExpect: About 24 V AC (often 24 to 28 V).