Baseboard or wall heater not working
Breaker and both legs, voltage at the heater, the line-voltage thermostat, then the element and limit.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
Electric baseboard and wall heaters are resistance elements, usually 240 V (some are 120 V). They’re controlled by a line-voltage thermostat, on the heater or on the wall, that switches the full heater current. A single-pole thermostat opens one leg; a double-pole one opens both and has a true off position. Each heater has an automatic-reset high limit that opens if it overheats, often because furniture or drapes block it. Wall heaters add a fan.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- What’s happening?
- One heater gives no heatTest: Measure voltage at the heaterExpect: The heater’s rated voltage: about 240 V (or 208 V or 120 V).
- Full voltage, no heatTest: Test the element and limitExpect: About R = V² ÷ W: 57.6 Ω for 1,000 W at 240 V, 38.4 Ω for 1,500 W. Limit closed when cool.
- Element reads OLBurned-out element
- Limit open when coolFailed high limit
- Both normalLoose or burned connection in the heater
- 0 V, or only one legTest: Check the thermostatExpect: Full voltage on the line side and on the load side.
- Voltage in, none outFailed line-voltage thermostat
- No voltage in, or one leg missingOpen wiring or a lost leg
- Full voltage, no heatTest: Test the element and limitExpect: About R = V² ÷ W: 57.6 Ω for 1,000 W at 240 V, 38.4 Ω for 1,500 W. Limit closed when cool.
- All heaters on a circuit are outCheck the 2-pole breaker for the heaters. What do you find?
- Tripped, and it trips againShort, ground fault or overloaded circuit
- Was off or tripped, works nowBreaker was off or tripped
- On and not trippedTest: Measure voltage at the heaterExpect: The heater’s rated voltage: about 240 V (or 208 V or 120 V).
- Full voltage, no heatTest: Test the element and limitExpect: About R = V² ÷ W: 57.6 Ω for 1,000 W at 240 V, 38.4 Ω for 1,500 W. Limit closed when cool.
- Element reads OLBurned-out element
- Limit open when coolFailed high limit
- Both normalLoose or burned connection in the heater
- 0 V, or only one legTest: Check the thermostatExpect: Full voltage on the line side and on the load side.
- Voltage in, none outFailed line-voltage thermostat
- No voltage in, or one leg missingOpen wiring or a lost leg
- Full voltage, no heatTest: Test the element and limitExpect: About R = V² ÷ W: 57.6 Ω for 1,000 W at 240 V, 38.4 Ω for 1,500 W. Limit closed when cool.
- Heats, but weaklyWrong voltage or blocked airflow
- Won’t shut offThermostat contacts stuck closed
- Cycles on and off, or smells hotHeater overheating and cycling on its limit
- One heater gives no heatTest: Measure voltage at the heaterExpect: The heater’s rated voltage: about 240 V (or 208 V or 120 V).