Breaker is hot, buzzing or smells burnt
Tell normal warmth from a loose connection that’s cooking the breaker or bus.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A breaker makes heat from current through its thermal element and at every connection: the wire under its lug and its jaws on the bus stab. A breaker carrying a heavy load can feel warm, and that’s normal. Heat out of line with the load, a buzz or a burnt smell means resistance at a connection, and that resistance oxidizes the metal and makes more heat until it arcs.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- What do you notice?
- Warm to the touchTest: Measure the load on the breakerExpect: Below 80% of the breaker rating for loads that run for hours (16 A on a 20 A).
- At or above the breaker ratingThe circuit is overloaded
- Well below the ratingTest: Compare temperatures with an infrared thermometer or cameraExpect: Similar temperatures to neighboring breakers at similar load, with no hot spot at the terminal or bus.
- At the wire terminal or wire endA loose or damaged wire connection at the breaker
- At the bus end of the breakerA poor connection between the breaker and the bus
- About the same as its neighborsNormal operating warmth
- Hot, can’t keep a hand on itTest: Measure the load on the breakerExpect: Below 80% of the breaker rating for loads that run for hours (16 A on a 20 A).
- At or above the breaker ratingThe circuit is overloaded
- Well below the ratingTest: Compare temperatures with an infrared thermometer or cameraExpect: Similar temperatures to neighboring breakers at similar load, with no hot spot at the terminal or bus.
- At the wire terminal or wire endA loose or damaged wire connection at the breaker
- At the bus end of the breakerA poor connection between the breaker and the bus
- About the same as its neighborsNormal operating warmth
- Buzzing or cracklingTurn off that circuit’s loads, then the breaker itself. Does the buzz stop?
- Stops when the load goes offTest: Compare temperatures with an infrared thermometer or cameraExpect: Similar temperatures to neighboring breakers at similar load, with no hot spot at the terminal or bus.
- At the wire terminal or wire endA loose or damaged wire connection at the breaker
- At the bus end of the breakerA poor connection between the breaker and the bus
- About the same as its neighborsNormal operating warmth
- Keeps buzzing with the breaker offThe noise isn’t from that breaker
- Stops when the load goes offTest: Compare temperatures with an infrared thermometer or cameraExpect: Similar temperatures to neighboring breakers at similar load, with no hot spot at the terminal or bus.
- Burnt smell, smoke or melted plasticActive overheating or arcing
- Warm to the touchTest: Measure the load on the breakerExpect: Below 80% of the breaker rating for loads that run for hours (16 A on a 20 A).