Current on the ground wire or water pipe
Use a clamp meter to find whether it’s coming from inside the building or from the utility side.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
Grounding and bonding conductors shouldn’t carry current in normal operation. Current there means neutral current has found a second path: a neutral-to-ground connection past the service, a metal water line shared with the neighbors, or a weak service neutral. That “objectionable current” causes tingles at plumbing, interference and heat, and it is a warning sign about the neutral.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- Where are you reading the current?
- Grounding electrode conductor or water pipe at the serviceTest: Clamp it with the main on, then offExpect: Little or no current with the main on or off.
- Current stays with the main offWith the main back on, do lights dim and brighten, or does voltage shift as big loads start?
- Yes, voltage shifts with loadA failing service neutral
- No, voltage is steadyNeighborhood neutral current on the water pipe
- Current drops to near zero with the main offTest: Clamp each circuit’s hots and neutral togetherExpect: Near 0 A on every circuit. Current that goes out on the hot comes back on the neutral.
- One branch circuit shows net currentTest: Look for a neutral-to-ground connectionExpect: OL (open). Loads left plugged in may show a high reading.
- Low ohms or continuityNeutral touching ground on this circuit
- OL or very highA load is leaking current to ground
- A subpanel feeder shows net currentNeutral bonded at or past a subpanel
- Every circuit reads near 0 AThe building’s own neutral current returning through the pipe
- One branch circuit shows net currentTest: Look for a neutral-to-ground connectionExpect: OL (open). Loads left plugged in may show a high reading.
- Current stays with the main offWith the main back on, do lights dim and brighten, or does voltage shift as big loads start?
- A ground wire or conduit on a feeder or branch circuitTest: Compare the circuit conductors and the groundExpect: Both near 0 A.
- Net current, and current on the groundTest: Look for a neutral-to-ground connectionExpect: OL (open). Loads left plugged in may show a high reading.
- Low ohms or continuityNeutral touching ground on this circuit
- OL or very highA load is leaking current to ground
- Net near zero, but current on the ground or conduitCurrent from another circuit or path
- A few milliamps onlyNormal leakage
- Net current, and current on the groundTest: Look for a neutral-to-ground connectionExpect: OL (open). Loads left plugged in may show a high reading.
- Grounding electrode conductor or water pipe at the serviceTest: Clamp it with the main on, then offExpect: Little or no current with the main on or off.