Wireman · Measure ground resistance: troubleshooting for electricians · 2023 NEC ·
Measure ground resistance
Fall-of-potential with stakes, or a clamp-on tester, and what each can and can’t tell you.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A grounding electrode’s resistance is how hard it is for current to spread from the rod into the earth around it. You can’t measure it with a multimeter; the earth needs a test current pushed through it to a far reference. Fall-of-potential uses stakes driven in a line from the rod. A clamp-on tester induces a test current around a loop, so it only works where the electrode is one of many parallel grounds, like a service on a utility multi-grounded neutral.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- What tester do you have?
- 3-pole or 4-pole tester with stakesCan the electrode be disconnected from the electrical system for the test?
- Yes, it can be isolatedTest: Run the fall-of-potential testExpect: The three readings agree closely.
- The three readings agreeWhat did it read?
- 25 Ω or lessResistance is 25 Ω or less
- More than 25 ΩResistance above 25 Ω
- Readings change a lot as P2 movesStakes are too close: no flat spot
- The three readings agreeWhat did it read?
- No, it stays connectedTest: Use the clamp-on testerExpect: A reading in ohms with little current on the conductor.
- A reading in ohmsWhat did it read?
- 25 Ω or lessResistance is 25 Ω or less
- More than 25 ΩResistance above 25 Ω
- Very low, under about 1 ΩYou measured a metal loop, not the earth
- Open or very highNo return path, or a broken connection
- Significant current on the conductorCurrent on the grounding electrode conductor
- A reading in ohmsWhat did it read?
- Yes, it can be isolatedTest: Run the fall-of-potential testExpect: The three readings agree closely.
- Clamp-on ground testerTest: Use the clamp-on testerExpect: A reading in ohms with little current on the conductor.
- A reading in ohmsWhat did it read?
- 25 Ω or lessResistance is 25 Ω or less
- More than 25 ΩResistance above 25 Ω
- Very low, under about 1 ΩYou measured a metal loop, not the earth
- Open or very highNo return path, or a broken connection
- Significant current on the conductorCurrent on the grounding electrode conductor
- A reading in ohmsWhat did it read?
- Only a multimeterA multimeter can’t measure earth resistance
- 3-pole or 4-pole tester with stakesCan the electrode be disconnected from the electrical system for the test?