Half the house is out
Some circuits dead, others fine, and 240 V appliances won’t run. Usually a lost leg.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A home gets two hot legs (L1 and L2) and a neutral. Each leg feeds every other breaker space, and 240 V loads use both. If one leg is lost, half the 120 V circuits die and every 240 V load stops or hums. If the lights are bright in some rooms and dim in others instead, that’s a neutral problem, which is more dangerous.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- What do you see?
- Some circuits dead, others work normallyTest: Measure at the main breakerExpect: About 120, 120 and 240 V on both sides.
- Line side missing a legLost leg from the utility
- Line side good, load side missing a legA failed main breaker
- Both sides goodThe problem is at the branch breakers
- Legs read unequal, like 150 / 90Open or loose service neutral
- Some lights very bright, others dimOpen or loose service neutral
- Only one appliance (dryer, range, A/C) won’t workTest: Measure at the appliance’s breakerExpect: About 240 V.
- 240 VThe supply is fine; the appliance has a fault
- About 0 V or 120 VOne pole of the 2-pole breaker isn’t passing power
- Some circuits dead, others work normallyTest: Measure at the main breakerExpect: About 120, 120 and 240 V on both sides.