Reading megger and winding test results
What a spot reading, a polarization index and winding resistances tell you about a motor.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
An insulation tester (megger) puts a high DC voltage between the windings and the frame and turns the small leakage current into a megohm reading. Good insulation reads high and keeps climbing as it polarizes; damp, dirty or damaged insulation reads low and stays flat. One number means little alone: compare it to the IEEE 43 minimums, correct it to 40 °C, and trend it against earlier tests on the same motor.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- Which reading do you want to understand?
- One-minute reading to groundCorrect the reading to 40 °C. Where does it fall?
- Below 5 MΩHas the motor been wet, sat idle in a damp place, or is it dirty or oily?
- YesMoisture or contamination
- No, it’s been clean and dryTest: Test the motor and cable separatelyExpect: Both at or above the minimum.
- Cable reads low, motor goodCable insulation fault
- Motor reads lowMotor winding insulation failure
- 5 MΩ or more, but far lower than past testsAbove minimum but falling
- 5 MΩ or more, similar to past testsInsulation passes
- Below 5 MΩHas the motor been wet, sat idle in a damp place, or is it dirty or oily?
- Polarization index (10 min ÷ 1 min)What is the polarization index?
- 2.0 or higherInsulation condition is good
- 1.5 to 2.0Marginal polarization index
- Below 1.5Has the motor been wet, sat idle in a damp place, or is it dirty or oily?
- YesMoisture or contamination
- No, it’s been clean and dryTest: Test the motor and cable separatelyExpect: Both at or above the minimum.
- Cable reads low, motor goodCable insulation fault
- Motor reads lowMotor winding insulation failure
- Winding resistance between leadsTest: Compare the three winding resistancesExpect: All three within about 5% of each other.
- Within about 5%Windings are balanced
- One pair more than 5% offWinding resistance unbalance
- One pair open (OL)Open winding
- One-minute reading to groundCorrect the reading to 40 °C. Where does it fall?