Mini-split error or won’t start
Power at each unit, the communication wiring, and what each kind of error code means.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A ductless mini-split has an indoor unit and an outdoor unit that talk over a communication wire. On many systems the outdoor unit gets power from its own breaker and feeds the indoor unit through the same interconnect cable that carries the signal; others power each unit separately. The outdoor unit uses an inverter board to drive the compressor, and its DC capacitors can hold a dangerous charge for minutes after power is off. Error codes differ by brand, but they fall into a few groups the manual will list.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- What is the system doing?
- Indoor unit dead, no lightsTest: Check power at the outdoor unitExpect: The nameplate voltage: usually about 240 V (or 208 V), or 120 V on smaller units.
- No voltage at the outdoor unitNo power to the system
- Voltage presentTest: Check power at the indoor unitExpect: The same supply voltage you read outdoors.
- Power at the indoor terminals, unit deadIndoor board or its fuse
- No power at the indoor terminalsDamaged interconnect cable
- Showing an error code or blinking lightLook up the code in the manual or on the label inside the cover. What kind of fault is it?
- CommunicationTest: Check the interconnect wiringExpect: Matching terminals at both ends, tight connections, and continuity on every conductor with no shorts between them.
- Terminals swapped or looseMiswired or loose interconnect
- Open or damaged conductorDamaged interconnect cable
- Wiring tests goodIndoor or outdoor board not communicating
- Sensor or thermistorA failed temperature sensor
- High pressure, high temperature or overcurrentThe unit shut itself down for protection
- Inverter, compressor drive or IPMInverter or compressor drive fault
- Fan motorIndoor or outdoor fan motor fault
- CommunicationTest: Check the interconnect wiringExpect: Matching terminals at both ends, tight connections, and continuity on every conductor with no shorts between them.
- Indoor runs, outdoor never startsTest: Check the interconnect wiringExpect: Matching terminals at both ends, tight connections, and continuity on every conductor with no shorts between them.
- Terminals swapped or looseMiswired or loose interconnect
- Open or damaged conductorDamaged interconnect cable
- Wiring tests goodIndoor or outdoor board not communicating
- Doesn’t respond to the remoteRemote or receiver
- Indoor unit dead, no lightsTest: Check power at the outdoor unitExpect: The nameplate voltage: usually about 240 V (or 208 V), or 120 V on smaller units.