Open or loose service neutral

Lights brighten and dim as loads switch, electronics die, or current shows up on water pipes. Find where the neutral is failing.

Before you start

How much electrical experience do you have?

This sets how much detail each step shows. You can change it any time.

How it works

On a 120/240 V service, the neutral carries only the difference between the two legs’ 120 V loads. If it opens, the loads on each leg end up in series across 240 V, and the voltage splits by how much load is on each side: the lightly loaded leg climbs well above 120 V and the heavy one sags. Whatever neutral current is left looks for another way back, through the grounding electrode conductor, metal water pipe, cable TV shields and even the neighbor’s service. Neutrals usually fail at a connection: the drop connectors, the meter socket neutral, the main panel neutral lug, or a corroded underground neutral.