240 V receptacle dead (dryer, range, welder)
Measure both legs at the receptacle to find a lost leg, a burned connection or an appliance fault.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A 240 V receptacle gets two hot legs, one from each side of the panel, with 240 V between them. Dryer and range receptacles (NEMA 14-30 and 14-50) add a neutral for 120 V parts like timers, lights and the dryer’s drum motor; welder and shop receptacles (6-20, 6-30, 6-50) have no neutral. With one leg missing, the 120 V parts can still run while heating elements and 240 V motors don’t, which is why a dryer can tumble without heat.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- What’s happening?
- Completely deadIs its 2-pole breaker tripped? Push it fully off, then on.
- It was tripped, works nowA tripped breaker
- It trips againA fault on the circuit or in the appliance
- Not trippedTest: Measure at the receptacleExpect: About 240 V across (208 V on a 208Y/120 V system) and about 120 V from each hot to neutral or ground.
- 240 V across, 120 V each sideThe receptacle is good; the appliance has the fault
- One hot reads 0 V to neutralTest: Measure at the breakerExpect: About 120, 120 and 240 V.
- Normal at the breakerA break between the breaker and the receptacle
- A leg missing at the breakerThe breaker isn’t passing one leg
- 0 V on everythingTest: Measure at the breakerExpect: About 120, 120 and 240 V.
- Normal at the breakerA break between the breaker and the receptacle
- A leg missing at the breakerThe breaker isn’t passing one leg
- About 208 V acrossA 208 V supply
- Runs but won’t heatTest: Measure at the receptacleExpect: About 240 V across (208 V on a 208Y/120 V system) and about 120 V from each hot to neutral or ground.
- 240 V across, 120 V each sideThe receptacle is good; the appliance has the fault
- One hot reads 0 V to neutralTest: Measure at the breakerExpect: About 120, 120 and 240 V.
- Normal at the breakerA break between the breaker and the receptacle
- A leg missing at the breakerThe breaker isn’t passing one leg
- 0 V on everythingTest: Measure at the breakerExpect: About 120, 120 and 240 V.
- Normal at the breakerA break between the breaker and the receptacle
- A leg missing at the breakerThe breaker isn’t passing one leg
- About 208 V acrossA 208 V supply
- Receptacle or plug is burned or meltedA burned receptacle or plug
- Completely deadIs its 2-pole breaker tripped? Push it fully off, then on.