Wireman · Soft starter faults: troubleshooting for electricians · 2023 NEC ·
Soft starter faults
Generic fault categories: supply, SCRs, bypass, start settings and load.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
A soft starter ramps a motor up by using SCRs to chop the voltage, then once the motor is up to speed, many models close a bypass contactor so the SCRs stop carrying current. It controls voltage, not frequency, so it reduces starting current and torque but can’t make the motor run at a different speed. Faults usually fall into a few groups: supply problems (phase loss, wrong rotation), power device problems (a shorted SCR), a start that takes too long, and overload.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- Which kind of fault does the display or manual describe?
- Phase loss or phase sequenceTest: Measure the incoming phasesExpect: Three equal readings within about 1–2% of each other and within the starter’s rated voltage range.
- One phase missing or lowLost or weak phase on the supply
- Balanced, but sequence is reversedPhase sequence reversed
- Balanced and correctLook at the motor and its leads
- Shorted SCR or power deviceTest: Check each pole for a shorted SCRExpect: A high reading on every pole, with all three similar. A few ohms or less means a shorted device.
- One pole reads very lowShorted SCR
- All three high and similarCheck for capacitors and the bypass contactor
- Start too long, stall or current limitHas the load or the start setting changed?
- Heavier load or a tight machineLoad too heavy for the start profile
- Settings were changed, or never tunedSettings don’t match the motor
- Overload or overcurrent while runningTest: Measure running currentExpect: At or below FLA and within about 10% of each other, with the starter’s setting matching the nameplate.
- Current high on all linesLoad too heavy for the start profile
- UnbalancedLook at the motor and its leads
- Normal, setting is lower than FLASettings don’t match the motor
- Phase loss or phase sequenceTest: Measure the incoming phasesExpect: Three equal readings within about 1–2% of each other and within the starter’s rated voltage range.