Wireman · Neutral and ground bonded at a subpanel: troubleshooting for electricians · 2023 NEC ·
Neutral and ground bonded at a subpanel
Find out where the bond belongs, remove the extra one and keep neutrals and grounds separate.
Before you start
How much electrical experience do you have?
This sets how much detail each step shows. You can change it any time.
Showing detail
How it works
The neutral and the ground are connected in exactly one place: the service disconnect, or the source or first disconnect of a separately derived system like a transformer. Downstream of that point they stay separate so neutral current returns only on the neutral. A bond at a subpanel puts part of the neutral current on the ground wires, conduit and anything they touch, and a loose feeder neutral can then put voltage on every metal enclosure.
Every question and answer in this guide. Tap “Step by step” to walk through it.
- What feeds this panel?
- It’s the first disconnect after the meterThe bond belongs here
- Another panel, or a meter-main with its own mainTest: Look at the neutral bar and the enclosureExpect: Neutral bar on insulators with no screw or strap, and grounds on a separate bar fastened to the enclosure.
- Bonding screw or strap installedDoes the feeder bring a ground back to the source panel?
- Yes, there’s a ground or metal conduitBond installed in a subpanel
- No, only hots and neutralSubpanel with no feeder ground
- No screw, but grounds and neutrals share a barGrounds landed on the neutral bar
- No bond and the bars are separateTest: Check the neutral bar is isolatedExpect: OL (open). Some lighting or electronic loads left connected can show a high reading; anything near 0 Ω is a bond.
- OL or very highNeutral is properly isolated
- Low ohms or continuityA neutral touches ground somewhere downstream
- Bonding screw or strap installedDoes the feeder bring a ground back to the source panel?
- A transformer secondaryWhere is the transformer’s neutral (X0) bonded to ground?
- Only in this panel (first disconnect)Bond at the first disconnect of a transformer
- At the transformer and also in this panelBonded at both the transformer and the panel
- Not bonded anywhereTransformer secondary isn’t bonded
- It’s in a separate buildingWhat does the feeder from the main building include?
- Two hots, neutral and ground (or metal conduit)Test: Look at the neutral bar and the enclosureExpect: Neutral bar on insulators with no screw or strap, and grounds on a separate bar fastened to the enclosure.
- Bonding screw or strap installedDoes the feeder bring a ground back to the source panel?
- Yes, there’s a ground or metal conduitBond installed in a subpanel
- No, only hots and neutralSubpanel with no feeder ground
- No screw, but grounds and neutrals share a barGrounds landed on the neutral bar
- No bond and the bars are separateTest: Check the neutral bar is isolatedExpect: OL (open). Some lighting or electronic loads left connected can show a high reading; anything near 0 Ω is a bond.
- OL or very highNeutral is properly isolated
- Low ohms or continuityA neutral touches ground somewhere downstream
- Bonding screw or strap installedDoes the feeder bring a ground back to the source panel?
- Only two hots and neutralOlder 3-wire feeder to another building
- Two hots, neutral and ground (or metal conduit)Test: Look at the neutral bar and the enclosureExpect: Neutral bar on insulators with no screw or strap, and grounds on a separate bar fastened to the enclosure.