Two-speed motor runs at the wrong speed

Check the speed contactor, its interlocks and the lead connections against the nameplate.

Before you start

How much electrical experience do you have?

This sets how much detail each step shows. You can change it any time.

How it works

Two-speed three-phase motors come in two common types. A consequent-pole motor has one winding that the starter reconnects to double the number of poles, so low speed is half of high speed (for example 1800/900 rpm). A two-winding motor has a separate winding for each speed, so the ratio can be anything (for example 1800/1200 rpm). The starter has a contactor for each speed, interlocked so both can’t close at once, and the leads must land exactly as the nameplate diagram shows.